CryoMechCompressorSwitchToOrFromTownWater
Instructions for switching a
CryoMech
compressor to/from town water.
Switch to Town Water
Switch back to Recirc Water
Tags
Comments
Switch to Town Water
Do it in this order to avoid tripping compressor
Open Town Water Out
Close Recirc water Out
Close Recirc Water In
Quickly Open Town Water In
Quickly open chiller bypass (red circle, picture below) to prevent chiller from crashing.
Switch back to Recirc Water
Open Recirc Water In
Close Town water In
Close Town Water Out
Quickly Open Recirc Water Out
Quickly close the chiller bypass.
Bypass valve locations. Red circle is recirculating water, blue is town water